Welcome to fuxibao automation official website!
+86-021-51601058
+86-189-6426-6865
classification
KFD2-VR4-Ex1.26 倍加福电压中继器现货供应

KFD2-VR4-Ex1.26 倍加福电压中继器现货供应

       倍加福电压中继器KFD2-VR4-Ex1.26,单通道隔离栅,振动传感器输入,电压输出0 V ... -20 V,Fuxb automation will serve you wholeheartedly! +86-021-51601058

Praise:

inquiry KFD2-VR4-Ex1.26 倍加福电压中继器现货供应
倍加福电压中继器KFD2-VR4-Ex1.26现货供应
KFD2-VR4-Ex1.26
产品特性
       ▷ 1通道隔离栅
       ▷ 24 V DC电源(电源导轨)
       ▷ 电压输入0 V ... -20 V
       ▷ 振动传感器输入
       ▷ 电压/电流场电源
       ▷ 电压输出0 V ... -20 V
       ▷ 符合SIL 2标准 符合IEC 61508

General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection Power Rail or terminals 11+, 12-
Rated voltage 19 ... 30 V DC
Ripple within the supply tolerance
Power dissipation ≤ 1.2 W
Power consumption ≤ 1.6 W
Input
Connection side field side
Connection terminals 4 (common), 1, 3 and 5 (supply -), 2 and 6 (signal -)
Input resistance 10 kΩ terminals 4 (common), 6-/2-
Output rated operating current terminals 4 (common), 5-: > 10 mA at -21 V or > 20 mA at -18 V
terminals 4 (common), 1-: 5.3 mA ±0.4 mA at -10 V
terminals 4 (common), 3-: 3.6 mA ±0.7 mA at -10 V, 20 °C (68 °F)
Transmission range -20 ... 0 V
Output
Connection side control side
Connection terminals 7-, 8+
Voltage -20 ... 0 V
Load ≥ 9 kΩ (3-wire sensor), ≥ 2 kΩ (2-wire sensor)
Output resistance 24 Ω typ., 27 Ω maximum
Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer.
Transfer characteristics
Cut-off frequency 10 kHz (-0,1 dB)
20 kHz (-1 dB)
Deviation DC transfer error (with 10 kΩ load) < 10mV
  After calibration additional error with AC superimposed is ±5 mV at 20 °C (68 °F) at any point within the span, provided that the alternating component of the input voltage is not excessive, e. g.
- square waves (0 ... 20 kHz): 5 Vpp
- sine waves (0 ... 20 kHz): the full span of 20 Vpp (= 100 g peak acceleration at 100 mV/g) is acceptable.
  Influence of ambient temperature (< 100 ppm of span)/K at any point within the span
Time delay relative to input 7.1 ±0.3 µs
Ripple in 200 kHz bandwidth < 20 mVrms
in 20 kHz bandwidth < 3 mVrms
Galvanic isolation
Output/power supply functional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elements LED
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2017
EN IEC 61326-3-2:2018
Degree of protection IEC 60529
Protection against electrical shock UL 61010-1
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 125 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate BAS 02 ATEX 7206
  Marking Ex-Hexagon II (1)GD, [Ex ia Ga] IIC, [Ex ia Da] IIIC, (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
  Input Ex ia Ga, Ex ia Da
  Voltage -26.4 V
  Current 90 mA
  Power 570 mW
Supply  
  Maximum safe voltage 253 V (Attention! The rated voltage can be lower.)
Output  
  Maximum safe voltage 253 V (Attention! The rated voltage is lower.)
EU-type examination certificate DMT 01 ATEX E 133
  Marking Ex-Hexagon I (M1) [Ex ia] I
Certificate TÜV 99 ATEX 1499 X
  Marking Ex-Hexagon II 3G Ex nA II T4 [device in zone 2]
Galvanic isolation  
  Input/Output safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V
  Input/power supply safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
International approvals
UL approval  
  Control drawing 116-0316 (cULus)
IECEx approval  
  IECEx certificate IECEx BAS 05.0078
IECEx BAS 10.0085X
  IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex nA II T4 Gc
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable.
Accessories
Optional accessories - power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)